Industrial Centrifugal Roof Fan (Standard & High-Pressure Series)

Heavy-duty industrial centrifugal roof fans designed for robust roof-mounted exhaust ventilation. Available in both Standard and High-Pressure configurations to meet diverse system resistance requirements.

• Series: Standard (General Exhaust) & High-Pressure
• Applications: Workshops, warehouses, and industrial plants
• Construction: Weather-resistant housing with square curb mounting base
• Performance: Multiple motor speeds and airflow capacities available

* Contact GORNOVENT with your required airflow and pressure for accurate duty point selection and CAD mounting dimensions.

Industrial Ventilation Equipment

Centrifugal Roof Fan Overview

GORNOVENT supplies centrifugal roof fans for industrial and commercial
exhaust ventilation systems. The product range includes standard
centrifugal roof fans and high-pressure centrifugal roof fans,
covering different airflow and pressure requirements.

Designed for roof-mounted air extraction, these fans can be considered
for workshops, warehouses, production buildings and other facilities
requiring mechanical exhaust ventilation. Model selection depends on
the required airflow, system resistance, installation dimensions
and operating conditions.

Centrifugal Roof Fans: Product Overview
GORNOVENT offers two centrifugal roof fan series:

  • Standard centrifugal roof fans: for general roof exhaust ventilation requirements.
  • High-pressure centrifugal roof fans: for ventilation systems requiring higher pressure.

Both series have separate performance and dimensional data. The correct model should be selected according to the required airflow and pressure at the same operating point.

Centrifugal Roof Fan Product Range

The two product series have different aerodynamic performance characteristics
and installation dimensions. Review the relevant performance table and
dimensional drawing before selecting a model.

Standard Centrifugal Roof Fans

The standard series is intended for general roof exhaust ventilation. It includes multiple impeller sizes, rotational speeds and motor power configurations.

Model selection should be based on the required airflow, system resistance and available installation space.

High-Pressure Centrifugal Roof Fans

The high-pressure series is intended for ventilation systems with higher pressure requirements. Its technical data provides multiple airflow and pressure operating points.

The selected model must be checked against the system duty point and the corresponding installation dimensions.

1. Standard Centrifugal Roof Fans

The standard centrifugal roof fan series covers multiple impeller sizes
and rotational speeds. The following tables provide the available
performance and dimensional specifications.

GORNOVENT standard centrifugal roof exhaust fan
Standard centrifugal roof fan.

Standard Series Performance Data

The table below lists the available airflow, pressure, rotational speed, motor power and weight for each configuration.

Standard centrifugal roof fan performance specifications
Model Speed (rpm) Airflow (m³/h) Static Pressure (Pa) Motor Power (kW) Weight (kg)
2.8 1440 1260 / 1040 100 / 150 0.18 18
2.8 2880 3080 / 2710 / 2300 100 / 300 / 500 0.55 20
3.15 1440 2050 / 1740 / 1450 80 / 150 / 200 0.18 19
3.15 2880 4370 / 3920 / 3470 150 / 400 / 600 1.1 24
3.55 1440 2880 / 2620 / 2320 100 / 150 / 200 0.25 21
3.55 2880 6270 / 5760 / 4930 150 / 400 / 700 2.2 29
4.0 960 2750 / 2590 / 2040 80 / 100 / 150 0.18 32
4.0 1440 4460 / 4030 / 3420 100 / 200 / 300 0.55 35
4.5 960 3940 / 3460 / 2760 100 / 150 / 200 0.25 34
4.5 1440 6280 / 5470 / 4680 150 / 300 / 400 1.1 39
5.0 720 4230 / 3870 / 2450 80 / 100 / 150 0.18 46
5.0 960 6120 / 5530 / 4470 100 / 150 / 200 0.55 46
5.0 1440 9650 / 8640 / 7740 150 / 300 / 400 1.5 52
5.6 720 4860 / 1800 150 / 200 0.37 67
5.6 960 9040 / 8460 / 7800 100 / 150 / 200 0.75 67
5.6 1440 14040 / 12960 / 11160 150 / 300 / 500 3.0 77
6.3 720 9090 / 7920 / 6210 100 / 150 / 200 0.75 80
6.3 960 12450 / 11760 / 9840 150 / 200 / 300 1.5 83
6.3 1440 20020 / 18970 / 17100 150 / 300 / 500 5.5 85
7.1 720 13800 / 12600 / 11400 100 / 150 / 200 1.1 96
7.1 960 17640 / 16170 / 14700 150 / 200 / 300 2.2 98
7.1 1440 27000 / 25400 / 24000 200 / 300 / 500 5.5 136
8.0 720 19800 / 18000 / 17200 100 / 150 / 200 2.2 146
8.0 960 26000 / 25020 / 24000 150 / 200 / 300 4.0 152
8.0 1440 40000 / 37800 / 35800 200 / 300 / 500 7.5 163

Note: Airflow and pressure values are listed in the corresponding sequence provided in the technical data. Confirm the required operating point against the approved fan performance curve before final selection.

Standard Series Dimensions

The following table provides the dimensional specifications of standard centrifugal roof fan models. All dimensions are in millimetres (mm).

Standard centrifugal roof fan dimensional specifications
Model D1 (mm) D2 (mm) H (mm) H1 (mm) Base A × A (mm)
3 310 690 700 80 430
3.5 360 800 720 80 480
4 410 920 930 80 520
4.5 460 920 940 80 570
5 510 1000 980 80 640
6 610 1200 1070 80 820
7 710 1460 1290 80 910
8 810 1610 1370 80 1050
10 1010 1840 1560 80 1300

Please verify the roof opening, mounting interface and overall clearance against the relevant dimensional drawing before installation.

2. High-Pressure Centrifugal Roof Fans

The high-pressure centrifugal roof fan series is intended for ventilation
systems with higher pressure requirements. The available performance data
covers models from 3 to 10, while the supplied dimensional drawing covers
models from 2.8 to 8.0.

GORNOVENT high-pressure centrifugal roof exhaust fan
High-pressure centrifugal roof fan. Replace this image with an actual product photograph.

High-Pressure Series Performance Data

The following table lists the available performance points for each model. Each airflow value is paired with the pressure value in the same position.

High-pressure centrifugal roof fan performance specifications
Model Speed (rpm) Airflow (m³/h) Static Pressure (Pa) Motor Power (kW) Noise Level dB(A) Weight (kg)
3 1450 878 / 925 / 1059 / 1130 / 1253 220 / 210 / 188 / 167 / 122 0.75 ≤57 88
3.5 1450 1395 / 1470 / 1682 / 1794 / 1990 299 / 285 / 256 / 227 / 166 1.1 ≤59 95
4 1450 1887 / 2083 / 2194 / 2510 / 2677 412 / 391 / 372 / 334 / 298 1.1 ≤62 115
4.5 1450 2966 / 3124 / 3574 / 3812 / 4514 495 / 471 / 423 / 376 / 231 1.1 ≤63 154
5 1450 4068 / 4285 / 4903 / 5438 / 6113 615 / 582 / 522 / 485 / 378 2.2 ≤64 195
6 960 5024 / 5512 / 6120 / 6782 / 7338 385 / 367 / 330 / 293 / 223 1.5 ≤65 234
7 960 8015 / 8804 / 9827 / 10836 / 11925 548 / 499 / 448 / 398 / 371 3.0 ≤68 292
8 960 12563 / 13565 / 14157 / 15824 / 16708 721 / 686 / 654 / 587 / 521 5.5 ≤70 374
10 720 22150 / 23298 / 26573 / 28395 / 31436 1072 / 1020 / 916 / 813 / 702 7.5 ≤72 396

Important: Each airflow value corresponds to the pressure value in the same position in the row. These values represent paired operating points, not independent airflow and pressure ranges. Confirm the required duty point against the approved fan performance curve.

High-Pressure Series Dimensions

The following dimensional data is transcribed from the supplied high-pressure series drawing. Models within the same group share the same listed dimensions. All dimensions are in millimetres (mm).

High-pressure centrifugal roof fan dimensional specifications
Model D1 (mm) D2 (mm) H (mm) H1 (mm) Base A × A (mm) B (mm)
2.8 500 690 615 50 605 370
3.15 500 690 615 50 605 370
3.55 500 690 615 50 605 370
4.0 700 935 722 50 880 645
4.5 700 935 722 50 880 645
5.0 700 935 722 50 880 645
5.6 800 1135 935 50 1170 935
6.3 800 1135 935 50 1170 935
7.1 970 1380 1135 50 1415 1185
8.0 970 1380 1135 50 1415 1185

The supplied dimensional drawing does not include model 10. Please request the corresponding drawing if model 10 is required. Do not use another model’s dimensions as a substitute without technical confirmation.

High-Pressure Series Dimensional Drawing

The drawing below shows the overall dimensions of the high-pressure centrifugal roof fan. Refer to the dimensional table and verify the mounting dimensions of the selected model before installation.

Overall dimensional drawing of a high-pressure centrifugal roof fan
Overall dimensional drawing — high-pressure centrifugal roof fan.

Typical Applications of Centrifugal Roof Fans

Centrifugal roof fans are used in mechanical exhaust ventilation systems where air is discharged through a roof-mounted fan assembly. The suitable configuration depends on the air volume, system resistance and air conditions.

Industrial Workshops

Exhaust ventilation for manufacturing workshops, production areas and industrial buildings.

Warehouses and Logistics Facilities

Roof-mounted exhaust ventilation for warehouses, storage buildings and logistics facilities.

Commercial Buildings

General exhaust ventilation for suitable commercial and public building ventilation systems.

Industrial Exhaust Systems

Air extraction applications where the fan must overcome resistance from ducts, bends, filters or other system components, subject to the selected fan’s performance capability.

How to Select the Right Centrifugal Roof Fan

A centrifugal roof fan should not be selected by model number or maximum airflow alone. The selected fan must meet the required airflow at the corresponding system pressure. Installation dimensions and operating conditions must also be checked.

1. Required Airflow

Specify the required air volume in m³/h. If the ventilation system operates under different conditions, provide the airflow required for each operating mode.

2. Required Static Pressure

Provide the estimated system resistance, including ductwork, bends, filters, dampers and other ventilation components. The fan must deliver the required airflow at the corresponding pressure.

3. Installation Dimensions

Check the roof opening, mounting base dimensions, overall height and available installation space. Use the dimensional drawing for the selected series to verify the interface dimensions.

4. Motor and Electrical Requirements

Confirm the supply voltage, frequency, number of phases, motor power and any requirements for speed control. If a variable frequency drive is required, specify the intended operating speed range.

5. Air and Operating Conditions

Provide the air temperature, dust content, humidity, corrosive characteristics and expected operating hours. These factors may affect the material selection, motor configuration and fan design.

Technical Information for a Roof Fan Inquiry

  • Required airflow (m³/h)
  • Required static pressure (Pa)
  • Air temperature and medium characteristics
  • Power supply voltage and frequency
  • Installation dimensions or roof opening drawing
  • Quantity and intended application
  • Any special material, control or environmental requirements

Standard vs. High-Pressure Centrifugal Roof Fans

Both series are centrifugal roof fans, but they have separate performance and dimensional specifications. The following comparison helps identify which technical data should be reviewed for a project.

Comparison of standard and high-pressure centrifugal roof fan series
Comparison Standard Series High-Pressure Series
Intended application General roof exhaust ventilation Ventilation requiring higher pressure
Performance models in supplied data 2.8–8.0 3–10
Dimensional models in supplied data 3–10 2.8–8.0
Dimensional parameters D1, D2, H, H1, Base A × A D1, D2, H, H1, Base A × A, B
Selection basis Airflow, pressure and installation dimensions Airflow, pressure and installation dimensions

The performance and dimensional tables refer to their respective product series. Do not use the dimensional data of one series to install the other series.

Industrial Fan Supply and Technical Support by GORNOVENT

GORNOVENT supplies industrial ventilation equipment for international customers and project applications. For centrifugal roof fan inquiries, we review the specified airflow, pressure, electrical requirements and installation dimensions before preparing a technical and commercial proposal.

  • Technical requirement review: Evaluation of airflow, pressure and operating conditions.
  • Multiple product configurations: Standard and high-pressure centrifugal roof fan options.
  • Project-based quotations: Proposals based on the customer’s technical specifications.
  • Dimensional information: Available dimensional data for model and installation verification.
  • Export supply support: Communication and technical coordination for international projects.

Frequently Asked Questions

What is a centrifugal roof fan?

A centrifugal roof fan is a roof-mounted ventilation fan that uses a centrifugal impeller to move air through an exhaust ventilation system. It is used in suitable industrial and commercial buildings to discharge indoor air through the roof.

What is the difference between standard and high-pressure roof fans?

The two series have different aerodynamic performance ranges and dimensional configurations. Standard models are intended for general roof exhaust applications, while high-pressure models are designed for systems requiring higher pressure. Selection must be based on the required airflow and pressure at the same operating point.

How do I choose the correct centrifugal roof fan model?

Provide the required airflow, pressure, air temperature, electrical supply and installation dimensions. The fan should be selected according to the system duty point and checked against the relevant performance curve.

Can GORNOVENT provide roof fan dimensional drawings?

Dimensional information is available for the models listed in the technical tables. Contact GORNOVENT if you need a specific model drawing or confirmation of mounting dimensions before installation.

Are standard and high-pressure roof fan dimensions interchangeable?

No. The two series have separate dimensional specifications. Always refer to the drawing for the exact series and model being selected.

What information is required for a quotation?

The main requirements are airflow and pressure. Please also provide the air medium, temperature, power supply, quantity and installation dimensions where available. A fan nameplate or existing equipment drawing can also help with technical evaluation.

Request a Centrifugal Roof Fan Quotation

Looking for a standard or high-pressure centrifugal roof fan for your ventilation project? Send GORNOVENT your required airflow, pressure, operating conditions and installation requirements.

Our team can review your specifications and provide a suitable technical proposal for further evaluation. You can also attach an existing fan nameplate, performance requirement or installation drawing.

Send Your Inquiry