HTFC-I & HTFC-II Series Low-Noise Cabinet Centrifugal Fan (No. 9 – No. 40)
GORNOVENT HTFC Series Cabinet Centrifugal Fans are high-efficiency, acoustically insulated box-type centrifugal blowers engineered for high-volume ventilation and emergency fire smoke extraction. Built around a low-noise forward-curved multi-blade centrifugal impeller, belt-drive transmission, and a sound-attenuating double-skin cabinet, the HTFC series spans 13 frame sizes (No. 9 to No. 40) delivering airflow from 1,650 to 112,619 m³/h and total pressure from 152 to 1,124 Pa.
Available in Type A (External Motor for Fire Smoke Exhaust) and Type B (Internal Motor for General HVAC), as well as HTFC-I (Single-Speed), HTFC-II (Dual-Speed), VFD-controlled (25–50 Hz), and Ex d IIB T4 Explosion-Proof variants, the HTFC series adapts seamlessly to basements, industrial plants, mining facilities, hotels, auditoriums, and commercial office towers.
280°C / 60-Min Fire Smoke Exhaust
12 Inlet / Outlet Orientations
ISO G4.0 Balanced | Ex d IIB T4 Option
Type A mounts the motor outside the hot airstream and passes GA211-2009 / CCCF high-temperature testing—operating continuously for 60 minutes at 280°C and 20 hours at 100°C.
Select HTFC-I for constant-load ventilation, HTFC-II with YDT 4/6-pole motors for dual-duty smoke/HVAC switching, or VFD inverter drives (recommended 25–50 Hz) for stepless energy savings.
Galvanized steel impellers and scrolls are die-formed and riveted/lock-seamed without welding distortion, dynamically balanced to ISO G4.0 inside a knock-down acoustic insulated cabinet.
Offers 12 standardized inlet/outlet discharge arrangements to fit tight mechanical rooms, plus optional Ex d IIB T4 explosion-proof construction, silencers, and G4/F7/HEPA filtration.
Type A (Fire Smoke Exhaust) vs. Type B (HVAC Ventilation)
Choose the motor mounting architecture that matches your fire safety code and acoustic requirements. Both Type A and Type B support 12 customizable inlet/outlet duct orientations (No. 1 to No. 12) shown below.
HTFC-I (Single-Speed) & HTFC-II (Dual-Speed) Performance Schedules
Representative operating envelopes for sizes No. 9 through No. 22 (380V / 3-Phase / 50 Hz). Full 13-size series up to No. 40 (112,619 m³/h, 1,124 Pa) and complete duty-point curves are available upon request.
| Model Size | Speed Range (r/min) | Airflow Range (m³/h) | Total Pressure (Pa) | Static Pressure (Pa) | YE2 Motor Range | Power (kW) | Weight (kg) | Noise dB(A) |
|---|---|---|---|---|---|---|---|---|
| HTFC-I No. 9 | 900 – 1,500 | 1,650 – 5,648 | 299 – 685 | 211 – 526 | YE2-801-4 to 100L1-4 | 0.55 – 2.2 | 84 – 97 | 53 – 63 |
| HTFC-I No. 10 | 1,100 – 1,500 | 2,950 – 6,498 | 315 – 708 | 230 – 617 | YE2-802-4 to 100L2-4 | 0.75 – 3.0 | 105 – 131 | 54 – 64 |
| HTFC-I No. 12 | 1,000 – 1,350 | 3,689 – 8,250 | 314 – 625 | 223 – 511 | YE2-90S-4 to 100L2-4 | 1.1 – 3.0 | 129 – 143 | 55 – 64 |
| HTFC-I No. 15 | 900 – 1,300 | 5,751 – 17,013 | 415 – 885 | 290 – 712 | YE2-100L1-4 to 132M-4 | 2.2 – 7.5 | 186 – 243 | 55 – 68 |
| HTFC-I No. 18 | 800 – 1,000 | 8,479 – 21,064 | 361 – 959 | 253 – 795 | YE2-100L2-4 to 160M-4 | 3.0 – 11.0 | 219 – 301 | 56 – 67 |
| HTFC-I No. 20 | 650 – 1,000 | 12,117 – 28,558 | 311 – 1,060 | 258 – 848 | YE2-112M-4 to 180M-4 | 4.0 – 18.5 | 295 – 435 | 60 – 72 |
| HTFC-I No. 22 | 550 – 600 | 7,485 – 22,400 | 387 – 488 | 290 – 438 | YE2-112M-4 to 132S-4 | 4.0 – 5.5 | 322 – 372 | 59 – 68 |
| Model Size | High / Low Speed (r/min) | High-Speed Airflow (m³/h) | Low-Speed Airflow (m³/h) | Total Pressure (Pa) | YDT Motor Model | Dual Power (kW) | Weight (kg) | Noise dB(A) |
|---|---|---|---|---|---|---|---|---|
| HTFC-II No. 10 | 1300/866 | 1400/933 | 3,250 – 6,498 | 2,166 – 4,330 | 237 – 708 | YDT-100L1 / 112M-4/6 | 2.2/0.7 – 3.2/1.1 | 121 – 131 | 57 – 64 |
| HTFC-II No. 12 | 1100/733 | 1200/800 | 5,440 – 8,250 | 3,625 – 5,500 | 183 – 625 | YDT-100L1 / 112M-4/6 | 2.2/0.7 – 3.2/1.1 | 131 – 143 | 56 – 62 |
| HTFC-II No. 15 | 975/650 – 1150/800 | 7,685 – 17,013 | 5,123 – 11,835 | 232 – 885 | YDT-132S to 160M-4/6 | 4.7/1.5 – 8.0/2.8 | 195 – 243 | 57 – 68 |
| HTFC-II No. 18 | 850/550 – 1200/800 | 10,349 – 23,358 | 6,697 – 15,572 | 259 – 1,180 | YDT-132M to 180M-4/6 | 6.0/2.0 – 15.5/5.1 | 252 – 301 | 57 – 67 |
| HTFC-II No. 20 | 800 / 550 | 15,914 – 23,646 | 10,941 – 16,257 | 246 – 703 | YDT-160M-4/6 | 8.0 / 2.8 | 334 | 61 – 68 |
HTFC Outline, Base Mounting & Duct Flange Dimensions (No. 9 – No. 40)
Reference outline drawings and complete millimeter dimension schedules for Type A (external motor) and Type B (internal motor) cabinets, including base channel anchor pitch and rectangular inlet/outlet flanges.
| Size (No.) | Height H / H’ | Base H1 | Type A Length L / L’ | Type A Pitch L1 / L1′ | Type B Length L / L’ | Type B Pitch L1 / L1′ | Width W | Bolt Pitch W1 | Base W2 |
|---|---|---|---|---|---|---|---|---|---|
| No. 9 | 580 / 505 | 50 | 640 / 600 | 680 / 640 | 850 / 810 | 930 / 890 | 640 | 730 | 790 |
| No. 10 | 620 / 550 | 50 | 690 / 650 | 720 / 680 | 920 / 880 | 1,000 / 960 | 700 | 790 | 850 |
| No. 12 | 720 / 625 | 50 | 740 / 700 | 780 / 740 | 1,050 / 1,010 | 1,150 / 1,110 | 820 | 910 | 970 |
| No. 15 | 830 / 740 | 50 | 900 / 860 | 940 / 900 | 1,180 / 1,140 | 1,300 / 1,260 | 940 | 1,030 | 1,090 |
| No. 18 | 930 / 825 | 50 | 1,020 / 980 | 1,100 / 1,060 | 1,280 / 1,240 | 1,400 / 1,360 | 1,100 | 1,190 | 1,250 |
| No. 20 | 1,043 / 933 | 63 | 1,100 / 1,060 | 1,180 / 1,140 | 1,450 / 1,410 | 1,600 / 1,560 | 1,250 | 1,340 | 1,400 |
| No. 22 | 1,143 / 1,013 | 63 | 1,250 / 1,210 | 1,320 / 1,280 | 1,550 / 1,510 | 1,700 / 1,660 | 1,360 | 1,450 | 1,510 |
| No. 25 | 1,323 / 1,163 | 63 | 1,380 / 1,340 | 1,500 / 1,460 | 1,700 / 1,660 | 1,900 / 1,860 | 1,520 | 1,610 | 1,670 |
| No. 28 | 1,460 / 1,290 | 80 | 1,480 / 1,435 | 1,600 / 1,555 | 1,820 / 1,775 | 2,050 / 2,005 | 1,650 | 1,740 | 1,800 |
| No. 30 | 1,570 / 1,370 | 80 | 1,580 / 1,535 | 1,700 / 1,655 | 1,920 / 1,875 | 2,150 / 2,105 | 1,720 | 1,810 | 1,870 |
| No. 33 | 1,690 / 1,510 | 100 | 1,780 / 1,730 | 1,900 / 1,850 | 2,050 / 2,000 | 2,350 / 2,300 | 1,860 | 1,950 | 2,010 |
| No. 36 | 1,840 / 1,630 | 100 | 1,900 / 1,850 | 2,050 / 2,000 | 2,200 / 2,150 | 2,500 / 2,450 | 2,000 | 2,090 | 2,150 |
| No. 40 | 1,950 / 1,950 | 100 | 1,900 / 1,850 | 1,900 / 1,850 | 2,800 / 2,750 | 3,100 / 3,050 | 2,000 | 2,090 | 2,150 |
| Size (No.) | Outlet Flange (a × b) | Inlet A × B (Orient. 1, 12) | Inlet A × B (Orient. 2, 3) | Inlet A × B (Orient. 4, 7, 8, 11) | Inlet A × B (Orient. 5, 6, 9, 10) |
|---|---|---|---|---|---|
| No. 9 | 280 × 280 | 560 × 450 | 560 × 375 | 560 × 560 | 560 × 450 |
| No. 10 | 320 × 320 | 620 × 490 | 620 × 420 | 620 × 610 | 610 × 490 |
| No. 12 | 380 × 380 | 740 × 590 | 740 × 495 | 740 × 660 | 660 × 590 |
| No. 15 | 460 × 460 | 860 × 700 | 880 × 610 | 880 × 820 | 820 × 700 |
| No. 18 | 540 × 540 | 1,020 × 800 | 1,020 × 695 | 1,020 × 940 | 940 × 800 |
| No. 20 | 600 × 600 | 1,170 × 900 | 1,170 × 790 | 1,170 × 1,020 | 1,020 × 900 |
| No. 22 | 640 × 640 | 1,280 × 1,000 | 1,280 × 870 | 1,280 × 1,170 | 1,170 × 1,000 |
| No. 25 | 730 × 730 | 1,440 × 1,180 | 1,440 × 1,020 | 1,440 × 1,300 | 1,300 × 1,180 |
| No. 28 | 800 × 800 | 1,550 × 1,280 | 1,550 × 1,110 | 1,550 × 1,380 | 1,380 × 1,280 |
| No. 30 | 880 × 880 | 1,620 × 1,390 | 1,620 × 1,190 | 1,620 × 1,480 | 1,480 × 1,390 |
| No. 33 | 940 × 940 | 1,760 × 1,490 | 1,760 × 1,310 | 1,760 × 1,680 | 1,680 × 1,490 |
| No. 36 | 1,050 × 1,050 | 1,900 × 1,640 | 1,900 × 1,430 | 1,900 × 1,800 | 1,800 × 1,640 |
| No. 40 | 1,150 × 1,150 | 1,900 × 1,750 | 1,900 × 1,750 | 1,900 × 1,800 | 1,800 × 1,750 |
Standard Factory Configuration & Optional Upgrades
Technical Specifications & Manufacturing Standards
How to Specify Your HTFC Cabinet Centrifugal Fan
Frequently Asked Questions
What is the difference between HTFC Type A and Type B cabinet fans?
Type A mounts the electric motor outside the acoustic cabinet so the motor stays cool and isolated from hot gases, making it certified for fire smoke exhaust (280°C for 60 minutes). Type B houses the motor inside the insulated box for maximum noise suppression during clean-air HVAC ventilation.
When should I choose an HTFC-II dual-speed fan over an HTFC-I single-speed fan?
Choose HTFC-II (dual-speed) when a single fan must serve two duties—such as underground parking garages, basements, or industrial halls that require quiet, low-power ventilation during normal hours and maximum-volume smoke extraction during a fire alarm.
Can HTFC cabinet fans be assembled on-site in tight basements or plant rooms?
Yes. The HTFC acoustic cabinet uses a modular cold-formed frame and bolted double-skin panel design. It can be disassembled and reassembled on-site to pass through standard doorways, elevators, or narrow underground corridors.
Is an explosion-proof version of the HTFC cabinet fan available?
Yes. GORNOVENT manufactures explosion-proof HTFC cabinet fans rated Ex d IIB T4 with flameproof motors and non-sparking construction for chemical workshops, paint booths, and other hazardous gas zones.